ARC
FLASH SAFETY REGULATIONS AND WORK PRACTICES: A FLASH REHASH
An electrician screws a circuit breaker onto a mounting plate, working
under no tag-out restrictions. One of the screws makes contact with
the line-side wiring behind the circuit breaker, penetrating the
wire insulation. The resulting short circuit vaporizes metal and
ionizes the air--an arc flash--causing a phase-to-phase fault. The
electrician receives second-degree burns from the arc flash. Because
there is no prejob analysis, neither the worker's proximity to potential
danger nor the necessity for appropriate Personal Protective Equipment
(PPE) is established.
Such an arc-flash explosion in and around electrical equipment
that requires burn treatment is said to occur five to 10 times
per day in the U.S., costing as much as $15.75 million per case
in direct and indirect outlays.
The basic distinction to be made between arc flash and ordinary
short-circuit, or bolted, contact is the heat and force, or incident
energy, generated by the arc. Temperatures as high as 35,000 degrees
Fahrenheit -- four times hotter than the sun's surface -- can
be achieved. Vaporized metal can expand 40,000 to 1, producing
a shattering blast. The physical conditions that produce arc faults
-- voltage x current x time -- along with distance from the arc,
which can be reduced by protective clothing, are the basic quantities
that are controlled and regulated to better insure protection
from an arc flash. Most regulations for improving worker safety
change over time as requirements become more familiar and economic
conditions rise and fall. Thus, safety regulations governing arc
flash are in a state of transition with regard to applying effective
protection.
THE REGULATIONS
Here's the bottom line: According to Occupational Safety and Health
Administration (OSHA) Standards 29-CFR, Part 1910 -- the electrical
industry's defining set of rules for dealing with arc flash --
equipment must be de-energized, that is, put in an electrically
safe condition, whenever possible before work begins. That includes
disconnecting every power source over 50 volts as well as all
control power; application of lockout/tag-out procedures; discharge
of all stored energy sources; and testing for safe conditions
by qualified personnel wearing appropriate PPE. This means, practically
speaking, that de-energization must occur when the bus voltage
is greater than 120 volts, since arc faults generally need in
excess of 120 volts to be sustained.
Some energy sources or live lines are not obvious, as in the
case of the worker described above. Potential danger should be
identified beforehand as part of a flash hazard analysis that
uses one-line drawings and nameplate specifications to determine
all areas where de-energization must occur. De-energization is
not always possible. However, for example, life support systems
at some facilities could shut down with an outage, and functional
testing of energized systems must, of course, be done with at
least part of the system online.
Further, the need to maintain a high level of production increasingly
demands that systems be worked hot. Those needs are countered
by expenses incurred through accidents, including worker injury
and unplanned outages from equipment damage, as well as the industry's
desire to keep its electricians safe. OSHA requires system calculations
based on the one-lines mentioned above as well as details of the
line sizes involved, along with minimum and maximum fault currents
supplied by the provider utility, to determine estimated short-circuit
energy and the flash protection boundary, or approach distance,
throughout the system. Those results then determine the extent
of PPE -- specifically, protective clothing -- that must be used.
The equations needed for those calculations are found in either
National Fire Protection Agency (NFPA) regulation 70E-2000 or
IEEE Standard 1584-2002. These calculations are not simple and
are usually achieved by a software program. Once the necessary
values have been established, OSHA requires labeling, that is,
field markers placed prominently on equipment that warn electrical
workers of potential arc flash hazards.
PROTECTIVE MEASURES
What follows next in the flash protection process is different
from place to place, depending on the nature of the equipment
involved and the governing facility policy. This is the coordination
of plant protective equipment -- breakers, disconnects, relays,
fuses -- with the energy situation at hand. How quickly and efficiently
this protective equipment responds to a short circuit to shut
the energy down can greatly minimize harm to personnel and damage
to equipment.
Note that the proper selection and adjustment of protective devices
won't, as is often thought, prevent an arc flash from occurring.
But the process of defining the appropriate time and current-limiting
response of protective devices can provide distinct advantages.
It can limit an outage to the portion of the system downstream
from the protective device, preventing the main breaker from tripping.
Further, and most critical to worker protection, it can better
assure that the necessary NFPA 70E category of protective clothing
is chosen. Overly conservative flash-hazard analyses that emphasize
preserving system reliability have traditionally established protective
equipment settings on the high side, with slower response times
tolerated and higher currents allowed. But slower reacting breakers
and fuses allow more arc energy to be produced before they trip.
That dictates using the most protective as well as cumbersome
gear, corresponding to NFPA Category 4.
More recent coordination studies have considered that arc fault
current is usually less than bolted fault current, allowing faster
equipment response and reducing the potential heat and force that
protective clothing must withstand. Such an evaluation might allow
electricians to wear a lower category of PPE that is also much
more comfortable and work friendly. Current-limiting circuit breakers
and lower rated fuses, coupled with other protective measures
like long-handled tools and infrared inspection windows on cabinets
for closed door inspection, can provide significantly improved
protection for electricians who must work with live equipment.
Thoughtful preventive measures -- de-energization when possible,
equipment selection and settings to minimize accidental arc exposure
-- can make a big difference in providing a more effective measure
of electrical worker safety.